Mode: HIVG 3600KV-540KJ
Related Standards:
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation (Ⅰ)
* ASTM D2518-Latest Electrical Insulation (Ⅱ)
Technical Parameters:
1) Rated Voltage:±3600kV
2) Rated stage voltage: ±200kV
3) Rated charging voltage: ±100kV
4) Rated energy:540kJ
5) Each stage impulse capacitor: 1.5μF/200kV
6) Stages: 18 stages
7) Stage energy:30kJ
8) Impulse voltage waveform parameter:
a) Standard lightning impulse voltage full-wave: 1.2±30%ms /50±20%ms,
Amplitude: ±3%, oscillation at peak value less than 5% of amplitude
b) Standard switching impulse wave: 250±20%ms /2500±60%ms
c) Standard chopping wave 2~5us, chopping wave disperstiveness deviation <=100ns.
d) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
9) Minimum output voltage efficiency
Standard lightning impulse voltage full-wave≥90% (No test object)Standard switching impulse wave≥70% (test object capacitance is 1000pF)
10) Synchronous range: stage voltage is between 20%~100% of rated voltage.
Positive and negative polarity synchronous range: less than 20%.
11) Synchronous discharge out of control rate <2% (Within the range: 10%~100% of rated voltage )
12) Sparking range: 15%-100%Un
13) Minimum output voltage: ≥10% rated voltage.
14) Charging voltage instability <±1.0%
15) Deviation between charging voltage and reference voltage <±1.0%
16) Working time:
When voltage above than 70% rated voltage, the systems can continuous working each 120s (charging and discharging).
When the voltage is below 70% of rated voltage, the system the system can continuous working each 90s(charging and discharging).
17) Voltage utilization factor
a). Lightning impulse full wave
When non-load, voltage utilization factor >=90%
When load is 3000pF, voltage utilization factor >=85%
b). Switching impulse wave
When load is 3000pF, voltage utilization factor >=60%
18) Generator overall height: 13500mm
19)Generator Overall weight: 13000kg.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.