800kV ~ 1600kV Range
HIVG 1600KV-80KJ Impulse Voltage Generator
Home > Systems > Impulse Generator > Impulse Generator > 800kV ~ 1600kV Range

HIVG 1600KV-80KJ Impulse Voltage Generator

Lead time: 75days

Mode: HIVG 1600KV-80KJ

Related Standards: 
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation ()
* ASTM D2518-Latest Electrical Insulation (
)

Technical Parameters: 
1) Rated Voltage: ±1600kV
2) Rated stage voltage: ±200kV
3) Rated charging voltage: ±100kV
4) Rated energy: 80kJ
5) Stages: 8stages
6) Generator overall capacitance 0.0625uF (pulse capacitor parameter: 100kV 1.0uF; 16units)
7) Stage energy: 10kJ
8) Impulse voltage waveform parameter:
     a) Under the condition of Load capacitance:400~2000pF
     b) Standard lightning impulse voltage full-wave
          T1=1.2μS±30%, T2=50μS±20%, oscillation at peak value less than 5% of amplitude
     c) Standard switching impulse voltage wave: 250±20%, 2500μS±60%
     d) Composite insulator steep wave impulse; >1000kV/us steep wave, amplitude 600kV
     e) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
9) Minimum output voltage >10%Un
10) Synchronous range: stage voltage is between 20%~100% of rated voltage.
       Positive and negative polarity synchronous range less than 20%.
11) Synchronous discharge out of control rate <2%
12) Sparking range: 10%-100%Un
13) Charging voltage instability <±1.0%
14) Voltage utilization factor:
       when load less than 1000pF, lightning impulse voltage utilizationfactor >=90%, switching impulse voltage utilization factor >=85%,
       when load less than 3000pF, the lightning impulse voltage utilization factor >=85%, switching impulse voltage utilization factor >=75%
15) Working time:
       When the voltage is above than 2/3 rated voltage, the system can continuous working each 120s (charging and discharging).
       When the voltage is below 2/3 of rated voltage, the system can continuous working each 60s (charging and discharging).


Principle Diagram: 

  