Tank Type
HTRS 200kV/2500kVA (100kV,30kV) Inductance Resonant Reactor
Home > Systems > Inductance Resonant > Inductance Resonant Reactor > Tank Type

HTRS 200kV/2500kVA (100kV,30kV) Inductance Resonant Reactor

Lead time: 120 days

Mode: HTRS 200kV/2500kVA (100kV,30kV)
Rated capacity:2500kVA            Rated frequency:50Hz±1Hz
Rated output voltage:200kV      Rated output voltage II: 100kV
Rated output voltage III:30kV    Rated output current: 12.5A  25A  83A
Inductance adjusting range and capacitor load range :
200kV/12.5A:50H~845H       0.012uf—0.2uf
100kV/25A :12.8H~253H      0.04uf—0.79uf
30kV/83A:1.15H~23H         0.45uf—8.8uf
PD level :Under 200kV≤20PC;
Load cycle:At rated load ,continue operation 1hour
Quality factor:20-100  Harmonic distortion :-20°~+40°
Dimension :L1900mm  W2100mm H2400mm  L(inculde length of bushing)3300mm
Weight: 12700kg  Cooling methods: ONAN
Insulation method :25# transformer oil .110kV grade
Structure: iron coil structure, user can change the reactance through adjusting open coil gaps, two epoxy tube, the steel bracket is made of stainless material in case of the reducing of quality factor which caused by eddy loss; pedestal has considered the heat which is caused by high‐intensity magnetic field; the resonant system designation has considered the expand with heat and contract with cold of the oil.

HTRS 200kV/2500kVA (100kV,30kV) Inductance Resonant Reactor, Inductance Resonant System HTRS 200kV/2500kVA (100kV,30kV) Inductance Resonant Reactor, Inductance Resonant System

HTRS 200kV/2500kVA (100kV,30kV) Inductance Resonant Reactor, Inductance Resonant System HTRS 200kV/2500kVA (100kV,30kV) Inductance Resonant Reactor, Inductance Resonant System 

External structure:
① Housing is tank type, and connected with flange at two terminals, resistant to impact, low leakage current and partial discharge, external color is sky blue.
② Withstand 20kPa atmosphere sealing test, no leakage, no permanent deformation.
③ Sealing ring is acrylate material for aviations, oil resistance and thermo stability.
Transmission component structure:
①Adopt good material, use 1Ni18T9 stainless steel, which can't transmit magnet, as guide rail.
②In order to reduce the noise, adopt 1Ni18T9 stainless steel, which can't transmit magnet, double lead screw to drag the flexible iron coil.