Applicable Standards: IEC 62067:2022, GB/T 22078.1
1.1 Basic Parameters (Rated voltage 500 kV, maximum system voltage Um=550 kV) Phase-to-earth voltage U0: 290 kV
Test voltage: 1.7U0 (493 kV, AC power frequency)
Duration: No less than 8760 hours (approximately 1 year)
Test frequency: 50 Hz (permissible range: 45 ~ 65 Hz)
Test object: Complete cable system, including cable and all types of accessories (terminations, joints, etc.), at least one set for each type.
Cable length: Minimum 100 m; the free cable section between accessories shall be no less than 10 m.
Installation method: Adopt single or combined laying modes according to actual operating conditions, including direct burial, duct laying, tunnel installation and overhead laying.

HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.